Solar String Sizing Calculator
String Sizing Calculator
Series/parallel string configuration with MPPT window and temperature correction. Adjust any input and the result updates live.
Inputs
Updates livePanel Datasheet Values (STC)
Inverter MPPT Parameters
Site Temperature Range
Results
LiveOptimal String Length (series)
Config: 12S × 2P per MPPT · valid range 6–17
Safe
Strings / MPPT
parallel
Total Panels
array count
System Size
kWp DC
Temperature-Corrected Voltages (per panel)
Safe — String design within all operating limits
“IEC 60364-7-712 requires that the open-circuit voltage of a PV string at minimum operating temperature must not exceed the maximum allowable DC voltage of the inverter. A 5% safety margin is recommended.”
About the String Sizing
String sizing sets how many solar modules connect in series per string so that the string voltage always stays within the inverter's MPPT operating window and never exceeds its maximum input voltage — across the full temperature range at your site.
Formula
Max modules/string = V_dc,max ÷ V_oc(at T_min)
- V_dc,max
- Inverter maximum DC input voltage (V)
- V_oc(T_min)
- Module open-circuit voltage at the coldest expected cell temperature (V) — Voc rises as temperature falls
How to calculate it
- 1Get the module Voc, Vmp and the temperature coefficient of voltage (β, %/°C) from the datasheet.
- 2Correct Voc up to the minimum site temperature (cold raises voltage — this sets the maximum series count).
- 3Correct Vmp down to the maximum cell temperature (hot lowers voltage — this sets the minimum series count to stay in the MPPT window).
- 4Choose a series count between the min and max that also respects the inverter's maximum string current.
Worked example
With a 1000 V inverter and modules at 49.5 V Voc corrected to ~54 V at cold-morning temperatures, the maximum is 1000 ÷ 54 ≈ 18 modules per string; the minimum is set by the MPPT lower bound at peak summer temperature.
What you can calculate
- Temp-corrected Voc
- MPPT window
- Series/parallel
- Safety margin
Standards & references
Key definitions
Definitions from the SolarPedia glossary
Frequently asked questions
Why does temperature matter for string sizing?
Solar module voltage rises as temperature falls. A string sized only for warm conditions can exceed the inverter's maximum input voltage on a cold, sunny morning — damaging the inverter or tripping it. Sizing must use the coldest expected temperature for the maximum count.
Ready to build your solar project?
Get free quotes from verified EPCs and installers across India.
You might also need
System Designer
Design custom solar system with component selection and layout optimization
OpenPanel Requirements
Calculate number of panels needed based on your energy consumption and roof space
OpenBattery Bank Sizing
LFP / NMC / Lead-Acid bank sizing with DoD, autonomy hours, temp derating, and S×P config
OpenSolar Plant Size
Size your plant in kWp from load (kWh/day) or available rooftop area
OpenInverter Sizing
Recommend inverter kVA from DC array kWp with DC:AC ratio and phase checks
OpenMPPT Window Check
Verify string voltage stays within inverter MPPT limits at Tmin and Tmax
Open